Cooling and Water Foundations for AI Infrastructure
Glossary
- ASHRAE Thermal Guidelines
- The reference published by ASHRAE technical committee TC 9.9 that sets recommended and allowable server inlet air conditions and the W-classes for liquid cooling supply temperatures.
- Coolant distribution unit (CDU)
- Equipment containing a heat exchanger, pumps, filters and controls that transfers heat from the server-side technology cooling loop to the building's facility water system while keeping the two loops separate.
- Direct-to-chip liquid cooling
- Cooling in which liquid flows through cold plates mounted on processors and other hot components, carrying heat away from the chip without relying on server airflow for those parts.
- Dry cooler
- A finned-coil heat exchanger that rejects heat to outdoor air with fans and no evaporation. It uses no water but can only cool fluid to a few degrees above ambient air temperature.
- Immersion cooling
- Cooling in which servers are submerged in a dielectric liquid. In single-phase systems the liquid stays liquid; in two-phase systems it boils on hot components and condenses on a coil.
- Power usage effectiveness (PUE)
- The ratio of total facility energy to the energy delivered to information technology equipment, defined by The Green Grid in 2007 and standardized as ISO/IEC 30134-2. Lower is better; 1.0 would mean zero overhead.
- Water usage effectiveness (WUE)
- Annual site water used for cooling and humidification divided by information technology equipment energy, in liters per kilowatt-hour. Introduced by The Green Grid in 2011 and standardized as ISO/IEC 30134-9.
- Water withdrawal versus consumption
- Withdrawal is all water taken from a source; consumption is the portion not returned, chiefly water evaporated. Evaporative cooling's main impact is consumption.